Product Details


Approvals

 UL Approval UL4703 600V 

18AWG~2AWG


Technical Data

Nominal voltage:600VAC  

Test voltage(U0):

U= 600V

18~10AWG, U0=3000V, 50HZ, 1Min

8~2AWG, U0=3500V, 50HZ, 1Min

Conductor maximum temperature: +120°C

Ambient temperature: –40°C up to +90°C

Relative permittivity: UL854

Cold bend test: UL854

Sunlight resistance: UL2556

Fire test: UL1581 VW-1

Heat distortion test :UL1581-560 (121±2℃)×1h, 2000g, ≤50%


Cable Construction

AWG Nominal Area
( mm2)
Conductor Construction
(n/mm)
Cable OD.
(mm)
Conductor Max.
Resistance AT
20℃(Ω/km)
Test Voltage
(KV, 50HZ/min))

18

0.823

16/0.254

5.10

23.20

6
16

1.31

26/0.254

5.50

14.60

6

14

2.08

41/0.254

5.90

8.96

6

12

3.31

48/0.300

6.40

5.64

6

10

5.261

105/0.254

7.20

3.546

7.5

8

8.367

168/0.254

9.00

2.23

7.5

6

13.3

266/0.254

10.10

1.403

7.5

4

21.15

420/0.254

11.50

0.882

7.5

2

33.62

665/0.254

13.30

0.5548

7.5

Note:The current-carrying capacity is under the situation of laying the single cable in air.