Approvals
TÜV Rheinland 2Pfg 1169
1.5mm2~35mm2 (Multiple color)
Technical Data
Nominal voltage: U0/U=600/1000V AC 1800V DC
Voltage test on completed cable: 6.5kV AC,15kV DC, 5min
Ambient temperature: –40°C up to +90°C
Max. Temperature at conductor: +120°C
The expected period of use is 25years
(Ambienttemperature: –40°C up to +90°C)
The permitted short-circuit-temperature refer to a period of 5s is +200℃
Bending radius: ≥4×φ(D<8mm) ≥6×φ(D≥8mm)
Resistance against acid and alkaline solution:EN60811-2-1
Cold bending test:EN60811-1-4
Weathering/UV-resistance: HD605/A1
O-zone resistance at complete cable:EN50396
Fire test: IEC60332-1
Smoke density: IEC 61034, EN 50268-2
Content of halogen acid gas: IEC 670754-1 EN50267-2-1
Cable Construction | |||||
Cross Section (mm2) |
Conductor Construction (n/mm) |
Conductor Stranded OD. (mm) |
Cable OD. (mm) |
Conductor Max. Resistance AT 20℃(Ω/km) |
Current Carrying Capacity AT 60℃(A) |
1.5 | 30/0.25 | 1.58 | 4.90 | 13.3 | 30 |
2.5 | 49/0.25 | 2.02 | 5.45 | 7.98 | 41 |
4.0 | 56/0.30 | 2.60 | 6.10 | 4.95 | 55 |
6.0 | 84/0.30 | 3.42 | 7.20 | 3.30 | 70 |
10 | 84/0.40 | 4.56 | 9.00 | 1.91 | 98 |
16 | 128/0.40 | 5.60 | 10.20 | 1.21 | 132 |
25 | 192/0.40 | 6.95 | 12.00 | 0.780 | 176 |
35 | 276/0.40 | 8.74 | 13.80 | 0.554 | 218 |
Note:The current-carrying capacity is under the situation of laying the single cable in air.